Copper vs Aluminium: Conductivity in Power Applications

Jul 01, 2024

Conductivity Numbers Side by Side

Property Copper Electrical-grade aluminium
Electrical conductivity 58.0 MS/m, 100 % IACS about 35.4 MS/m, 61 % IACS
Electrical resistivity at 20 C 0.017241 ohm.mm2/m about 0.028264 ohm.mm2/m
Thermal conductivity 385-401 W/(m.K) about 205-237 W/(m.K)
Density 8.96 g/cm3 2.70 g/cm3
Relative conductivity per unit mass 1.00 about 2.0

Aluminium's disadvantage in conductivity is offset by its much lower density. Dividing conductivity by density gives copper about 6.5 MS/m per g/cm3 and aluminium about 13.1, so an aluminium conductor carries roughly twice the current of a copper conductor of the same mass, while copper carries about 1.6 times the current of an aluminium conductor of the same cross-section. This single arithmetic relationship explains most of the application split between the two metals.

Volume Basis Versus Mass Basis

The choice between the metals depends on which resource the design constrains. Where space is fixed, as in a motor slot, a transformer winding, a switchboard or the underfloor of a vehicle, copper wins because it delivers more ampacity per unit volume and removes heat more effectively through its higher thermal conductivity. Where mass is the binding constraint, as on an overhead line between pylons, aluminium wins because the same current can be carried with a lighter conductor and lighter supporting structures, and the larger diameter is not penalised by wind loading in the way that a heavier conductor would be. Aluminium also costs less per tonne, which matters most in long-run, low-density installations.

Where the Lines Are Drawn in Practice

Overhead transmission and distribution lines are built from aluminium and aluminium-alloy conductors, often steel-reinforced, to standards such as ASTM B231/B231M and ASTM B232/B232M. Motors, generators, transformers, switchgear, high-current battery interconnects and electric-vehicle busbars are built from copper, with busbar ordered to ASTM B187/B187M in grades such as C11000, and with the temper chosen for stiffness and bending requirements. Between those extremes there is a zone where either metal can be made to work, and the decision then turns on termination cost, corrosion environment and thermal margin rather than on the metal itself.

Connection, Corrosion and Standard Requirements

Three technical issues govern mixed-metal and aluminium installations. The first is galvanic corrosion: aluminium connected directly to copper in a wet or saline environment will corrode at the joint, so bimetallic transition plates or copper-aluminium connectors are specified. The second is creep and cold flow in aluminium terminations, which demands re-torque schedules and belleville washers or specifically designed connectors to keep joint resistance stable over time. The third is oxide growth on aluminium, which requires abrasion or an oxide-penetrating compound immediately before termination. Conductor standards address these requirements directly: ASTM B1 for hard-drawn copper wire, ASTM B3 for soft or annealed copper wire, ASTM B8 for concentric-lay-stranded copper conductors, and IEC 60228 or GB/T 3956 for the classification of insulated cable conductors, which also fixes the class 2 or class 5 stranding that determines flexibility.

Buying Conductor-Grade Copper

Material for conductor manufacture is ordered as cathode to GB/T 467-2010, ASTM B115 or EN 1978, and as wire rod to GB/T 3952 or ASTM B49. The properties that matter downstream are conductivity at or above 100 % IACS, controlled oxygen content, low levels of phosphorus and other conductivity-damaging impurities, surface cleanliness and freedom from laps, seams and slivers that cause wire breaks in drawing. Conductivity verification on delivery is by resistivity measurement to ASTM B193 or by the eddy-current method of ASTM E1004, and the certificate should record the test temperature because conductivity is temperature dependent. For applications such as vacuum components, high-frequency conductors or large rotating machines, an oxygen-free grade to ASTM B170 or ASTM F68 is specified instead, since it holds conductivity at 101-102 % IACS and avoids hydrogen embrittlement during brazing and annealing.

Frequently Asked Questions

Q: Is copper twice as conductive as aluminium?

A: By volume, copper is about 1.6 times as conductive, at 100 % IACS against about 61 % for electrical-grade aluminium; on an equal-mass basis aluminium carries roughly twice the current.

Q: Why is aluminium used for overhead power lines instead of copper?

A: Weight and cost; an aluminium conductor of the same mass carries about twice the current of copper, which reduces the load on towers and insulators over long spans.

Q: Why is copper still used in motors and transformers?

A: Space and heat: copper carries more current per unit volume and removes heat better, so it allows smaller windings with lower temperature rise for the same output.

Q: How should copper and aluminium be joined?

A: With bimetallic transition plates or specifically designed copper-aluminium connectors, and in wet or saline locations with a joint design that excludes electrolyte, because direct contact causes galvanic corrosion.

Q: What conductivity should conductor-grade copper rod show?

A: Wire rod is normally certified at or above 100 % IACS, equivalent to 58.0 MS/m at 20 C, verified by ASTM B193 or ASTM E1004.