What Is The Difference Between The Temperature Resistance Ratings Of Cables, in National, American And European Standards?

Dec 28, 2023

In the design, selection, production and sales of wire and cable, often encountered many temperature parameters, such as 90 ℃, 105 ℃, 125 ℃, 150 ℃ and so on. These parameters in the industry's common name are called temperature resistance level parameters, that these parameters are how to come? Why is the aging temperature different for the same 90℃ temperature resistance grade material? What is the relationship between aging temperature and temperature resistance level? What is the definition of the maximum permissible long-term working temperature of the conductor of the insulation? What is the temperature index? What is the temperature rating of a material? Can silane cross-linking compounds meet a temperature rating of 125°C?

To answer the above questions, first of all, we need to understand the standard system, because different standard systems have different definitions of temperature resistance level. Our common standard system mainly includes national standards (and industry standards), UL standards, EN/IEC standards and so on.

As the preparation of national standards and industry standards, a lot of content is reference and reference to international standards, so let's look at the UL standard or EN / IEC standards on the provisions of the temperature resistance level.

First, UL standard

UL standard, the common temperature resistance level is 60 ℃, 70 ℃, 80 ℃, 90 ℃, 105 ℃, 125 ℃ and 150 ℃. How do these temperature resistance ratings come about? Is it the long-term operating temperature of the conductor? In fact, these so-called temperature ratings are called rating temperature in the UL standard. It is not the long-term operating temperature of the conductor.

Rated Operating Temperature

Rated temperature in the UL standard in accordance with the confirmation of the formula 1.1 to determine (see UL 2556-2007 in Chapter 4.3 long-term aging of materials section). Specific process is to first assume that the material of a temperature rating, such as 105 ℃, and then calculated in accordance with Formula 1.1 oven test temperature of 112 ℃, respectively, in such a test temperature will be placed in the sample 90 days, 120 days and 150 days, to get the sample elongation rate of change and the number of days of aging data, and then by the method of least squares to deduce the number of days of aging and the elongation at break of the linear relationship between the linear relationship, and then based on the linear relationship deduced in the oven, the elongation at the time of aging, and then the elongation at the time of aging. Then the linear relationship between the number of aging days and elongation at break was deduced by the least squares method, and then the elongation at break of the samples was deduced based on this linear relationship when the samples were aging for 300 days at this oven temperature (112°C).

If the change in elongation at break is less than 50%, the material is considered to be able to reach the assumed rated temperature. If the change in elongation at break is greater than 50%, the material is considered to be rated at a temperature that does not reach the assumed rated temperature, and a new rated temperature needs to be assumed to continue the above test.

It can be seen, in the UL standard system, if the use of the inverse method can be considered as follows: a material at a certain temperature A ℃ aging 300 days, the elongation rate of change is not more than 50%, and then the temperature A minus 5.463, and then divided by 1.02, to get a temperature of B ℃, it can be recognized that the material can reach the temperature of B ℃ of the rated temperature.

This rated temperature is by no means the maximum long-term operating temperature of the conductor allowed by the insulation layer. Because the long-term maximum operating temperature in the "long-term" should actually be the life of the cable at this operating temperature, at least to calculate the unit of years, such as photovoltaic cable standard EN50618, the life of the cable is designed for 25 years, UL standards in the rated temperature will be generally higher than the conductor of the long-term maximum operating temperature.

Short-term aging temperature

The short-term aging temperature of the material, that is, we usually most common in the standard 7 days, 10 days, etc., such as 105 ℃ material, aging conditions for 136 ℃ × 7 days. So what is the relationship between this and the rated temperature? In the UL standard, the short-term aging temperature is obtained by the long-term experience of using the material, but also summarized some methods to confirm. Such as in UL2556-2007 standard 4.3.5.6 chapter and appendix D in this way to determine a material's short-term aging temperature. First select a rated temperature, aging temperature and aging time according to Table 1-1.

If the elongation change after aging of the material tested under the above conditions is greater than 50%, the material is considered to be acceptable for determining the aging temperature according to these conditions, and if the elongation change is greater than 50%, the material's rated temperature and short-term aging temperature are to be lowered by one grade.

Second, EN / IEC standards
In the EN / IEC standards, rarely like the UL standard to see the rated temperature (rating temperature), instead of the conductor long-term operating temperature (operation temperature) or temperature index. So what is the difference between these two temperatures?
In fact, in the EN/IEC standard system, the evaluation of the temperature rating of the cable is mainly in accordance with EN 60216 or IEC 60216 to evaluate. This standard mainly evaluates the thermal life of insulating materials. The evaluation method is to carry out aging test of the material at different temperatures, and take the change rate of elongation at break of 50% as the end point of aging, and derive the number of aging days of the material at different temperatures. Then through the linear regression of the aging days and aging temperature to do linear correlation processing, resulting in a linear relationship curve. Then the maximum working temperature is determined according to the life of the cable, or according to the long-term working temperature, to determine the life of the cable.

The temperature index, on the other hand, is the temperature corresponding to the 50% change in elongation at break of the insulation material after thermal aging for 20000H. Taking the PV cable standard EN 50618:2014 as an example, the design life of the cable is 25 years, the long-term working temperature is 90℃, while the temperature index is 120℃. The short-term aging temperature of the insulation material is also derived from the above linear relationship.

Therefore, the aging temperature for insulation materials in EN 50618:2014 is 150°C. This aging temperature is very close to the aging temperature of 158°C for materials rated at 125°C in the UL standard series.

Through the above analysis, it is not difficult to see that the same long-term operating temperature of the conductor may not have the same required aging temperature due to the different design life of the cable. In the same long-term operating temperature, the shorter the design life of the cable, the shorter the short-term aging temperature of the insulation material can be required the lower.

For example, in IEC 60502-1:2004, the maximum long-term operating temperature of XLPE insulation is 90℃, while the aging temperature of this material is 135℃. The 135°C is close to the UL standard aging temperature of 136°C, which is rated at 105°C, but it is much lower than the aging temperature of EN 50618:2014, which also requires a long-term maximum operating temperature of 90°C. Although in 60502-1:2004 did not find the design life of the cable, but the design life of the two cables is certainly different.

Third, national standards and industry standards

China's national standards and industry standards in the preparation process, a lot of content is reference and reference to the UL standard or EN/IEC standards. But because it is a multi-party reference, so some of the expression I think is inaccurate. For example, in GB/T 32129-2015, JB/T 10436-2004, JB/T 10491.1-2004, both materials and wires, the temperature resistance level are 90 ℃, 105 ℃, 125 ℃ and 150 ℃, which is obviously borrowed from the UL standard system. However, the expression for heat resistance is the maximum permissible long-term operating temperature of the conductor. This expression of heat resistance and obvious reference to the IEC standard system.
In the IEC standard system, the maximum long-term operating temperature of the conductor should be associated with the design life of the cable, but these national standards and line standards, there is no cable life of the statement. So this "applicable cable conductor long-term maximum allowable operating temperature is 90 ℃, 105 ℃, 125 ℃ and 150 ℃" statement is open to question.

2.5 mm T1 Copper WireT1 Copper Metal WireT1 Copper Wire

 

 

Then silane cross-linked XLPE can reach 125 ℃ temperature rating? A more rigorous answer should be silane cross-linked XLPE can reach the UL standard specified in the 125 ℃ temperature rating, because in UL1581 Chapter 40 of the insulation and sheath materials in the General Provisions, has been clearly put forward not to make provisions for the chemical composition of the material. And whether the long-term maximum working of XLPE conductor can reach 125℃, which is related to the design life of the cable and the use of occasions, at present, no relevant information can be found to systematically evaluate the life of this material. By short-term aging to speculate, if the design life of the cable is 25 years, its allowable long-term maximum temperature of the conductor can certainly be greater than 90 ℃.

In IEC standards, conventional power cables, building wires and even solar cables are not designed for a maximum long-term operating temperature of the conductor of more than 90 ° C, but it does not mean that the materials used in such cables can not be used for a maximum long-term operating temperature of more than 90 ° C. The maximum long-term operating temperature of the conductor can be greater than 90 ° C, but it can be greater than 90 ° C. Nor can it be said that irradiation crosslinking material can reach 125 ℃ temperature resistance level, and silane crosslinking material can not reach 125 ℃ temperature resistance level, such an expression is not justified.
In short, a material can reach a certain temperature level, can not simply answer yes or no, but to combine the material temperature rating evaluation method or the design life of the cable to consider, can not be mixed with several standard systems used indiscriminately.